Overview of Microgrid Results

Microgrid Name Generation Bus Minimum 1 hr Load (kW) Average 1 hr Load (kW) Average Daytime 1 hr Load (kW) Maximum 1 hr Load (kW) Maximum 1 hr Critical Load (kW) Existing Fossil Generation (kW) New Fossil Generation (kW) Existing Solar (kW) New Solar (kW) Existing Battery Power (kW) Existing Battery Energy Storage (kWh) New Battery Power (kW) New Battery Energy Storage (kWh) Existing Wind (kW) New Wind (kW) Total Generation on Microgrid (kW) Renewable Generation (% of Annual kWh) Emissions (Yr 1 Tons CO2) Emissions Reduction (Yr 1 % CO2) Average Outage Survived (h) O+M Costs (Yr 1 $ before tax) CapEx ($) CapEx after Tax Incentives ($) Net Present Value ($)
mg0 634 60 178 247 306 306 0 119 440 161 79 307 52 150 0 0 851 48 404 19 52 13,263 734,438 550,031 -277,710
mg1 675 243 453 574 861 713 265 164 0 1,312 0 0 185 664 0 0 1,926 41 1,174 41 495 33,348 3,027,222 1,995,701 -30,463
mg2 646 25 139 215 385 385 0 164 0 608 0 0 185 500 0 0 957 55 273 55 934 14,546 1,753,006 1,236,988 -353,239
Summary None 389 769 1,036 1,548 1,404 265 447 440 2,081 79 307 422 1,314 0 0 3,734 45 1,851 40 52 61,157 5,514,666 3,782,720 -661,412

Report Generated

2024-03-04 19:18:30.453152

User Warnings

Pre-existing battery battery_634_existing will not be utilized to support loads in microgrid mg0.
Supporting critical loads across microgrids assumes an AMI metering system. If not currently installed, add budget for the creation of an AMI system.
Supporting critical loads across microgrids assumes the ability to remotely disconnect 3-phase loads.

Distribution Upgrades needed to create Microgrids

Microgrid Location Recommended Upgrade Cost Estimate ($)
mg0 mg0 Microgrid Design 100,000
mg0 mg0 Microgrid Controls 100,000
mg0 632633 SCADA disconnect switch 50,000
mg0 634a_data_center AMI disconnect meter 300
mg0 634b_radar AMI disconnect meter 300
mg0 634c_atc_tower AMI disconnect meter 300
mg1 mg1 Microgrid Design 100,000
mg1 mg1 Microgrid Controls 100,000
mg1 671692 SCADA disconnect switch 50,000
mg1 675a_hospital 3-phase relay 20,000
mg1 675b_residential1 3-phase relay 20,000
mg1 675c_residential1 3-phase relay 20,000
mg1 692_warehouse2 3-phase relay 20,000
mg2 mg2 Microgrid Design 100,000
mg2 mg2 Microgrid Controls 100,000
mg2 632645 SCADA disconnect switch 50,000
mg2 645_hangar AMI disconnect meter 300
mg2 646_office AMI disconnect meter 300

Description